← Our Services / Door Entry & Access Management
Access Control
Card, fob and keypad access control systems, specified to release safely on activation of your fire detection system. Based in Stockport, covering Greater Manchester, Cheshire and the Peak District, with sites nationwide.
Single-door setups through to networked, multi-site access control — card, fob, keypad or biometric readers, specified to how people actually move through the building.
Where an access-controlled door forms part of a means of escape, or a fire door is held open electrically, it has to be released reliably when the fire alarm operates. BS 7273‑4 sets out how the electrical interface between the two systems is designed, installed, commissioned and maintained, and it sits directly at the overlap between our two specialisms.
We're based in Stockport and install access control systems across Greater Manchester, Cheshire and the Peak District, with sites covered further afield across the UK.
BS 7273‑4
BS 7273-4 gives recommendations for the electrical control arrangements that unlock, release or open doors in the event of fire, including the interface with the fire detection and alarm system; the current edition is BS 7273-4:2015+A2:2023. It does not recommend whether such mechanisms should be used in any particular premises, which is a matter for the fire risk assessment and the enforcing authorities. Because we design fire alarms ourselves, the interlock is specified as part of the system from day one.
Technical Specification
Access methods & door hardware.
Two separate decisions go into every door: how someone gets through it, and how the hardware behaves if power's lost or the fire alarm activates.
| Element | Detail |
|---|---|
| Card/fob | Proximity credential presented to a reader — easy to issue, revoke and audit per user. |
| Keypad | Shared PIN or code — lower cost, but harder to audit who actually went through since the code isn't tied to one person. |
| Biometric | Fingerprint or similar — ties access to the individual with no credential to lose or share, at a higher cost per door. Biometric data processed to identify a person is special category data under the UK GDPR, so it needs a lawful basis and an Article 9 condition as well as the ICO's other expectations. |
| Fail-safe | Unlocks automatically on loss of power to the lock. BS 7273‑4 describes this as essential for electronically secured doors and powered sliding doors on means of escape, and recommends that the lock does not need power to unlock, so that people are never locked in. |
| Fail-secure | Stays locked on loss of power. Used where security takes precedence and the door is not on a means of escape — a comms cupboard or a store, for example. |
Standards
How a door is released.
The fire alarm and the access control system have to work together, and BS 7273‑4 sets out how reliably.
Categories of actuation
BS 7273‑4 divides release arrangements into Critical (Category A), Standard (Category B) and Indirect (Category C) actuation, according to the faults under which the door still releases. The category for each door is selected from Annex B, stated in the specification and recorded on the commissioning certificate. For electronically locked doors, Annex B gives Category A for premises occupied by or open to the public, for hostels, care premises and hospitals, and for schools, while offices, factories and warehouses where staff are trained in the fire safety provisions may use any category.
Failure conditions
Categories A and B both release on an open or short circuit in the critical signal path, within 120 seconds, and on a fall in the supply voltage to the release mechanism below the level at which it can operate, within 3 seconds (60 seconds for self-closing fire doors). Category A goes further and also covers the simultaneous failure of the normal and standby power supplies to the fire alarm system and the disablement of any single call point, detector or zone on which the door release depends. Powered sliding doors on means of escape are arranged to open on failure of the power supply that operates them.
Access control as the interface
Where the release signal is generated by the access control system’s own controller and not directly by the fire alarm panel, the arrangement is Indirect actuation (Category C). BS 7273‑4 notes that the additional complexity inherently reduces reliability and may mean the arrangement has to be limited or given additional safeguards, and recommends that the access control system and its components conform to BS EN 60839‑11‑1 and BS EN 50133‑2‑1. Annex B also notes that enforcing authorities may not accept electronically secured doors on means of escape in some premises.
Manual emergency release
A clearly labelled manual release control, readily distinguishable from a fire alarm call point, is recommended close to each electronically secured door on a means of escape, other than in places of lawful detention (cl 7.2). It is connected directly in series with the power supply to the release mechanism so that it works whatever the state of the fire alarm system, and the door has to release within 3 seconds of operation (cl 11.2). The 2021 amendment revised the arrangements for these controls, partly to reduce the chance of people mistaking them for call points, and we work to the current edition.
What's Included
Scope of work.
- Single-door to multi-site networked systems
- Card, fob, keypad & biometric readers
- Fire-alarm interlocked release to BS 7273-4, with manual emergency door release where recommended
- Integration with CCTV & intruder alarm
- Visitor / permission management options
Other Specialisms
The rest of the picture.
Fire and security systems rarely stop at one discipline — here's everything else we cover.
Fire Alarms
Design, installation, commissioning and maintenance of fire detection and alarm systems, specified to the layout and use of your building.
Fire Alarms →Fire Extinguishers
Supply, siting and annual servicing of portable fire extinguishers, matched to the fire risks present in your building.
Fire Extinguishers →Emergency Lighting
Emergency lighting that works when the power doesn't — designed, installed and tested to BS 5266‑1, so escape routes stay lit and exits stay visible.
Emergency Lighting →CCTV
Camera systems specified to suit the site, with remote viewing options — from a single entrance camera to a fully networked, monitored setup.
CCTV →Intruder Alarms
Detection and alarm systems protecting premises against unauthorised access — from single-zone setups for smaller units to multi-zone systems across larger sites.
Intruder Alarms →Drawing Design
Zone plans, system schematics and as-wired drawings for new and existing systems — available as a standalone service for systems that need documentation brought up to date.
Drawing Design →Sprinkler Monitoring
Electrical monitoring of wet and dry sprinkler installations — flow, valve position, tank level and pump status brought back to a dedicated monitoring panel, with the signals passed on to your fire alarm system and, where required, to an ARC.
Sprinkler Monitoring →ARC Monitoring
Signalling from fire and intruder alarms to an accredited Alarm Receiving Centre, with police URN application support for intruder alarms.
ARC Monitoring →Need access control?