Emergency Lighting
Emergency lighting that works when the power doesn't — designed, installed and tested to BS 5266‑1, so escape routes stay lit and exits stay visible. Based in Stockport, covering Greater Manchester, Cheshire and the Peak District, with sites nationwide.
Escape routes, open areas and high-risk task areas covered to BS 5266‑1 — using self-contained luminaires or a central battery system, depending on what suits the building. Either way, the point is the same: enough light to get out safely if the mains supply fails.
BS 5266‑1 recommends a functional test of every luminaire at least monthly and a full rated-duration test at least annually, with a visual inspection each year; the rated duration is 1 hour or 3 hours depending on the premises (see below), so the annual test runs for whichever duration the system was designed to. The test routine and the inspection and test certificate are set out in BS EN 50172 (BS 5266‑8), and every test and any remedial work should be entered in the log book. We carry out the testing on schedule and provide the paperwork.
We're based in Stockport and cover emergency lighting installation and testing across Greater Manchester, Cheshire and the Peak District, with sites further afield across the UK.
BS 5266‑1 & BS EN 50172
BS 5266‑1 is the code of practice for the design and installation of emergency lighting in premises; it was fully revised and republished by BSI on 29 October 2025, replacing the 2016 edition, and now also covers local area and standby lighting alongside escape lighting. Routine testing and certification follow BS EN 50172 (BS 5266‑8): a monthly function test, an annual full rated-duration test and a written record of each.
Technical Specification
Coverage & duration.
BS 5266‑1, working with BS EN 1838, sets minimum illuminance by area type, and a duration the system has to sustain once the mains supply fails.
| Area | Requirement |
|---|---|
| Escape routes | Not less than 1 lx along the centre line of a route up to 2 m wide. Points of emphasis — each exit door, stairs (so each flight is lit directly), changes of level, changes of direction and intersections, fire-fighting equipment, call points and first-aid points — are lit locally, generally with a luminaire within 2 m. |
| Open areas | Anti-panic lighting for rooms over 60 m², or smaller rooms a risk assessment shows need it: not less than 0.5 lx across the floor, excluding a 0.5 m border, so people can reach the escape route. |
| High-risk task areas | Not less than 10% of the normal lighting at the point of risk, with detailed requirements in BS EN 1838, and the light available quickly (within 0.5 s) — enough for someone to safely shut down a hazardous process or machine before leaving. |
| Duration | 1 hour is the minimum, and is appropriate only where the premises are evacuated immediately on supply failure and not reoccupied until the batteries have fully recharged. 3 hours is used where premises are not evacuated immediately — sleeping accommodation and places of entertainment, for example — or where they may be reoccupied as soon as the supply is restored. |
| System type | Self-contained luminaires (each with its own battery) or a central power supply system (one battery bank or generator feeding multiple luminaires) — operating as maintained (lit continuously) or non-maintained (lit only on supply failure), or combined with a normal luminaire; maintained operation is normally used where the normal lighting may be dimmed or switched off while the premises are occupied. |
Exact provision depends on the building's layout, use and risk assessment — figures above are summarised from BS 5266‑1:2016 and BS EN 1838 and should be confirmed against a site-specific design and the current edition, BS 5266‑1:2025.
What's Included
Scope of work.
- Design to BS 5266-1 coverage requirements
- Self-contained & central battery system installation
- Monthly function testing and log book entries
- Annual full rated-duration testing (1 or 3 hours, to suit the system)
- Fault repair & luminaire replacement
- Testing certificates for your compliance record
Viaduct Fire’s Notes
Escape isn’t the only task.
Our view, from the engineer’s side of the job.
Emergency lighting is there to help people get out when the supply fails, whether that is a fire or a blackout, and most of a design is about exactly that: lit routes, lit exits, lit signs. But the people in a building are rarely just standing waiting to leave. They are in the middle of something when the lights go, and for some activities the first thing they need is enough light to stop doing it safely. A gym is the example we use. Someone running on a treadmill when the supply fails is on moving equipment, in a room that has just gone dark, and needs to bring themselves to a stop and step off safely before they can think about finding the exit. If the only emergency lighting in that room is aimed at the door, the escape route is lit and the person who has to get to it is not.
BS 5266‑1 recognises this as a separate category, high risk task area lighting, for the safety of people involved in a potentially dangerous process or situation and to allow a proper shut-down before they leave, set at not less than 10% of the normal lighting at the point of risk and available within 0.5 seconds. The 2025 edition goes further and brings local area lighting and standby lighting inside its scope alongside escape lighting. Whether a particular space needs it is a matter for the fire risk assessment, but the question has to be asked, and it is easy to miss when a layout is drawn up around the routes and exits and the equipment on the floor is not looked at.
Beyond gyms, we look for the same thing in workshops with machine tools, commercial kitchens with hot plates and fryers, plant rooms and switch rooms, laboratories, and anywhere else a person could be left exposed to a hazard by the lights failing at a bad moment. Viaduct Fire takes a holistic approach: we survey how the building is actually used, not just where the doors are, and design the emergency lighting around the people in it. If you are not sure whether your site has areas like this, get in touch and we will look at it with you.
Other Specialisms
The rest of the picture.
Fire and security systems rarely stop at one discipline — here's everything else we cover.
Fire Alarms
Design, installation, commissioning and maintenance of fire detection and alarm systems, specified to the layout and use of your building.
Fire Alarms →Fire Extinguishers
Supply, siting and annual servicing of portable fire extinguishers, matched to the fire risks present in your building.
Fire Extinguishers →CCTV
Camera systems specified to suit the site, with remote viewing options — from a single entrance camera to a fully networked, monitored setup.
CCTV →Intruder Alarms
Detection and alarm systems protecting premises against unauthorised access — from single-zone setups for smaller units to multi-zone systems across larger sites.
Intruder Alarms →Drawing Design
Zone plans, system schematics and as-wired drawings for new and existing systems — available as a standalone service for systems that need documentation brought up to date.
Drawing Design →Access Control
Card, fob and keypad access control systems, specified to release safely on activation of your fire detection system.
Access Control →Sprinkler Monitoring
Electrical monitoring of wet and dry sprinkler installations — flow, valve position, tank level and pump status brought back to a dedicated monitoring panel, with the signals passed on to your fire alarm system and, where required, to an ARC.
Sprinkler Monitoring →ARC Monitoring
Signalling from fire and intruder alarms to an accredited Alarm Receiving Centre, with police URN application support for intruder alarms.
ARC Monitoring →Need emergency lighting?
Tell us about the site and what you need — we'll get back to you with a straight answer.