← Our Services / ARC Monitoring & Emergency Response
ARC Monitoring
Connecting your fire and intruder alarm systems to an accredited Alarm Receiving Centre — so a fire, intruder or fault signal reaches a keyholder, and where the conditions are met the police or the fire and rescue service, even when nobody is on site to hear it.
An ARC (Alarm Receiving Centre) is a monitoring centre, staffed around the clock, that receives the signals from your alarm system over an alarm transmission path. This means a fire, fault or intruder signal reaches someone outside working hours, and even where the on‑site sounder alone wouldn't reach anyone. Signalling is commonly dual‑path, for example broadband with a mobile network backup, so that the loss of one path does not cut the system off. We specify and install the signalling equipment, connect it to an accredited ARC partner, and support the registration paperwork.
What the connection delivers differs for fire alarms and intruder alarms, covered separately below.
Fig. 01 — Signal path from site to ARC to responder (illustrative)
Fire Alarms
ARC monitoring & fire alarms.
Whether a fire alarm system signals to an ARC is a design decision that BS 5839‑1 asks the designer to settle with the purchaser or user (cl 14.5). Where early summoning of the fire and rescue service is deemed critical to the safety of occupants, for example on the basis of a fire risk assessment, it recommends automatic transmission unless there are reliable arrangements for people in the building to summon the fire and rescue service (cl 14.6); it also recommends it in residential care premises (cl 14.7), in Category P systems other than in continuously occupied premises (cl 14.8), and in Category L systems in non‑domestic premises in multiple occupation unless occupants can summon the fire and rescue service at all times (cl 14.9). The signalling also bears on the standby battery: for a Category P system, a power supply fault that is automatically transmitted to an ARC, which then notifies a keyholder and the agreed service provider immediately, allows a standby capacity of 24 hours in place of up to 72 (cl 24.3.5); see our battery standby calculator for the detail.
Automatic attendance by the fire and rescue service is a separate matter. BS 5839‑1 says that in occupied buildings the primary means of summoning the fire and rescue service should always be a call by the occupants using the public emergency call system (cl 14.2), and that systems that automatically transmit a pre‑recorded message direct to the fire and rescue service should not be used (cl 14.3). Whether a service attends on a signal passed on by an ARC is for each fire and rescue service to decide, and policies differ between services. We confirm what your local service requires as part of specifying the system.
Intruder Alarms
ARC monitoring & police response.
For intruder alarms, ARC monitoring is what makes police response possible: the police give a response only to a system that has a Unique Reference Number (URN) and is reported through an approved ARC. Qualifying for a URN means meeting the conditions of the National Police Chiefs’ Council (NPCC) security systems policy, which include:
- Installation and maintenance certificated by a UKAS‑accredited certification body, such as NSI or SSAIB
- Installation to PD 6662, with confirmation to BS 8243 for new systems; the grade is set by the risk assessment and your insurer
- A confirmed‑alarm arrangement to BS 8243, such as sequential detection, or audio or video verification
- Monitoring by an ARC operating to BS EN 50518
- At least two trained keyholders, reachable by telephone, with transport and access to all parts of the premises, able to attend within 20 minutes; a keysafe is not an acceptable substitute
The installer or maintainer submits the notice of intention to install to the local police force, the occupier completes the site form, and the URN is issued and owned by the police; the ARC quotes it when passing an activation on, and the fee is paid by the system user. A URN gives the premises Level 1 response, which the policy describes as normally immediate but determined by demand, priorities and resources at the time, and which therefore cannot be guaranteed. It is also conditional on a clean record: under the March 2024 version of the policy, three false calls within a rolling twelve months withdraw police response, leaving keyholder response only, and two failures by keyholders to attend in twelve months can mean three months without a response. The policy has been revised since, with changes to the false alarm definitions and administrative processes, so we confirm the current thresholds with the force. Managing the false‑alarm rate is part of the ongoing service, alongside the initial registration.
Standards
What the signalling has to do.
BS 5839‑1 sets the requirements for fire alarm signalling, the NPCC policy for police response to intruder alarms.
Fire signalling — BS 5839‑1 cl 14
Where a fire alarm signal is transmitted, an indication should reach the ARC within 90 seconds on a Category L system and 120 seconds on a Category P system (cl 14.17 and 14.18), and a catastrophic failure of the transmission system should be indicated at the ARC and at the control panel, within 3 minutes for Category L and 31 minutes for Category P. Faults in the transmission equipment or path are displayed on the panel (cl 14.20), the equipment area is protected by automatic fire detection (cl 14.12), and transmission must not depend on, or be prevented by, silencing the sounders (cl 14.13).
The ARC — BS 5839‑1 cl 14.11
An ARC to which fire alarm signals are relayed should conform to BS EN 50518 and BS 9518 in respect of processing the signals, and have an agreement with the fire and rescue service to pass them on. The standard notes that certification of an ARC does not always cover fire alarm signals as opposed to intruder alarm signals, so it is worth confirming that the ARC’s scope includes them. It also gives the ARC all relevant information about the premises, including whether people sleep there (cl 14.10).
NPCC security systems policy
The NPCC policy, Police Operational Advice and Security Industry Requirements for Response to Security Systems, applies to installers offering police response systems and to ARCs in England, Wales and Northern Ireland. It was updated in 2025 and the NPCC’s policy page lists a further update dated June 2026, so we work to the edition in force when the system is registered and tell you where it affects the design.
Signalling paths & the analogue switch-off
BS 5839‑1 notes that the risk from loss of communications can be reduced by a dual path alarm transmission system, with the greatest resilience when the two paths use different technologies, for example an IP connection and mobile telephone technology; loss of both paths is displayed as a fault at the panel (cl 14.20). Openreach plans to switch off the analogue telephone network on 31 January 2027, after which a communicator that signals over a copper telephone line will no longer reach an ARC, so any system still using one needs its signalling reviewed before then.
Viaduct Fire’s Notes
Signalling is only as good as the path it relies on.
Our view, from the engineer’s side of the job.
Fire signals routed through the intruder panel. When we take over a fire alarm system, we often find that its monitoring is routed through the intruder alarm panel, using the intruder system’s communicator to carry the fire signal to the ARC. BS 5839‑1 allows this and deals with it directly: where fire alarm signals are routed via the routing equipment of an intruder and hold‑up alarm system, the standby power supplies for that equipment should conform to cl 24.3, and the power supply unit should conform to BS EN 54‑4 or BS EN 50131‑6 grade 4 (cl 14.16). It is acceptable, but it brings considerations that a standalone fire alarm communicator does not. The first is the battery. A standby battery that was adequate for the intruder system on its own has to be checked against the standby duty the fire alarm standard requires of the routing equipment, rather than assumed to be sufficient because the communicator has been working. The second is servicing. In our experience intruder alarms are not serviced to the same standard as fire alarms, so the equipment that carries the fire signal can sit outside the regime that keeps the rest of the fire alarm system proven, and a fire signal reaching the ARC should be tested at every fire alarm service visit, whichever panel it travels through.
The third consideration is access. The communicator’s programming and its isolation or disablement are normally controlled by codes held by the intruder alarm company, and the fire alarm service provider often has none of them. If the fire company cannot test the signal, cannot isolate monitoring for works without calling someone else, and cannot see that someone has disabled it, then it is not in a position to be sure that the fire alarm will summon help. The standard expects a fault in the transmission equipment or path to be displayed on the fire alarm control panel (cl 14.20), through a suitably monitored interface (cl 14.19), and that only works if the interface from the fire panel to the routing equipment has been installed and checked as part of the fire system.
Dual path, and what it actually protects against. It is very common to find a system described as dual path that has two mobile radio paths, because that is the easiest arrangement to install: no cabling back to a router is needed. In our view that gives little more than a single path. The failure that matters most, loss of the mobile network or of a usable signal at the premises, takes both paths out at once, and two SIMs on different networks guard only against one operator’s outage while both paths still depend on mobile radio coverage at the site. The note to cl 14.20 of BS 5839‑1 makes the same point in different words: for the greatest resilience the two paths should use different technologies, for example an IP connection and mobile telephone technology. That is what we look to install. We fit a GSM or radio unit alongside an IP path wherever we can, so that if the mobile network goes down the system still communicates over IP, and if the broadband goes down it still communicates over the mobile network.
What's Included
Scope of work.
- Dual‑path signalling equipment specified & installed, fire and/or intruder
- Connection to an accredited, 24/7‑staffed Alarm Receiving Centre
- Police URN application support for intruder alarm response
- Confirmed‑alarm setup (sequential detection / audio or visual verification) to BS 8243
- Keyholder liaison and cover arrangements
- Ongoing false‑alarm management to protect police/ARC response status
Other Specialisms
The rest of the picture.
Fire and security systems rarely stop at one discipline — here's everything else we cover.
Fire Alarms
Design, installation, commissioning and maintenance of fire detection and alarm systems, specified to the layout and use of your building.
Fire Alarms →Fire Extinguishers
Supply, siting and annual servicing of portable fire extinguishers, matched to the fire risks present in your building.
Fire Extinguishers →Emergency Lighting
Emergency lighting that works when the power doesn't — designed, installed and tested to BS 5266‑1, so escape routes stay lit and exits stay visible.
Emergency Lighting →CCTV
Camera systems specified to suit the site, with remote viewing options — from a single entrance camera to a fully networked, monitored setup.
CCTV →Intruder Alarms
Detection and alarm systems protecting premises against unauthorised access — from single-zone setups for smaller units to multi-zone systems across larger sites.
Intruder Alarms →Drawing Design
Zone plans, system schematics and as-wired drawings for new and existing systems — available as a standalone service for systems that need documentation brought up to date.
Drawing Design →Access Control
Card, fob and keypad access control systems, specified to release safely on activation of your fire detection system.
Access Control →Sprinkler Monitoring
Electrical monitoring of wet and dry sprinkler installations — flow, valve position, tank level and pump status brought back to a dedicated monitoring panel, with the signals passed on to your fire alarm system and, where required, to an ARC.
Sprinkler Monitoring →Need ARC monitoring?
Tell us about the site and what you're trying to achieve — fire, intruder, or both — and we'll get back to you with a straight answer.