← Our Services  /  Documentation & Compliance Drawings

Drawing Design

Zone plans, system schematics and as-wired drawings for new and existing systems — available as a standalone service for systems that need documentation brought up to date. Based in Stockport, covering Greater Manchester, Cheshire and the Peak District, with sites nationwide.

Full drawing packages to support new installations, upgrades and compliance sign-off — zone plans showing the division of the building into detection zones, system schematics, cause-and-effect matrices, and as-wired drawings (the as-fitted drawings of BS 5839‑1) reflecting exactly what's installed on site, including the actual cable routes.

Available as a standalone service too — if your existing system's documentation is missing, out of date, or was never done properly, we can survey the site and produce it fresh.

We're based in Stockport and provide drawing and design services across Greater Manchester, Cheshire and the Peak District, with sites covered further afield across the UK.

PANEL RECEPTION OFFICE STORE PLANT RM WC SMOKE DETECTOR HEAT DETECTOR CALL POINT SOUNDER VIADUCT FIRE LTD — SAMPLE DRAWING

Fig. 04 — Illustrative zone plan & as-wired layout (generic sample)

Technical Specification

Document types.

Four related documents, each doing a different job — a full package usually needs all four. For fire detection and alarm systems the requirements come from BS 5839‑1:2025.

DocumentShows
Zone planA diagrammatic representation of the building showing at least the entrances, the main circulation areas and the division into detection zones, printed, correctly orientated to the position of someone standing at the panel, and mounted on or adjacent to the control and indicating equipment (BS 5839‑1 cl 22.2.5). It tells whoever responds to an alarm where the fire is, whether they are staff or the fire and rescue service.
SchematicThe system's electrical circuits and interconnections — panel, power supplies, interfaces — independent of the building layout. A schematic of the order in which devices are wired is not a substitute for an as-fitted drawing, other than on small, simple systems.
Cause-and-effect matrixHow the system responds to each input: which detectors, call points or other inputs cause which outputs, such as sounders, beacons, door release, plant shutdown, lift recall or signalling to an alarm receiving centre. BS 5839‑1 (cl 38.1) expects either a matrix or a text description of the cause and effect to be provided at handover, and anyone modifying a system needs the current configuration, including the full cause-and-effect logic (cl 46.1.4).
As-wired drawingWhat is actually installed on site, as opposed to what was originally designed. BS 5839‑1 (cl 38.1) calls these as-fitted drawings and expects them to show the positions of all control, indicating and power supply equipment, all manual call points, detectors and alarm devices, equipment needing routine attention such as short-circuit isolators and remote indicators, and the type, size and actual route of the cables.

Drawings need to be updated whenever the system is extended or altered (cl 46.1.8), and anyone modifying a system should have access to the current as-fitted drawings (cl 46.1.4). Kept current, they are the first thing an engineer, ours or anyone else's, reaches for when something needs investigating or extending.

Standards

What BS 5839‑1 expects.

Drawings aren’t paperwork for its own sake — the standard treats them as part of the safety of the system.

DOC‑01

Zone plan — cl 22.2.5

A diagrammatic representation of the building must be on or adjacent to the indicating equipment, as an illuminated mimic diagram, a VDU with an appropriate back-up, or a printed, correctly orientated zone plan. The standard notes that in certain fatal fires, including one with 14 deaths, some or all of the deaths could have been avoided if a zone plan had been provided close to the panel. It also lists the absence of one, in premises with more than one zone on any storey, among the departures so detrimental to life safety that they should not be accepted as variations (cl 6.6).

DOC‑02

As-fitted drawings — cl 38.1

As-fitted drawings are part of the documentation that has to be provided to the purchaser or user at handover, alongside operating and maintenance instructions, a cause-and-effect matrix or description and a logbook. The standard says the preparation and accuracy of these drawings matter in particular, because without them maintenance or later modification of the system might be difficult.

DOC‑03

Who provides it — cl 5.7

Before an order is placed, the responsibility for providing the zone plan should be clearly defined, agreed and documented. The commentary records that this responsibility is often left ill-defined, so that a suitable zone plan is missing when the installation is handed over. We agree it with you at the start of a job.

DOC‑04

Servicing & alterations

At each annual servicing visit, a check is made that a suitable zone plan is provided on or adjacent to all control and repeat indicating equipment, and that the zone identification reported on the panel matches the one on the plan (cl 43.3.24 and 43.3.25). When changes are made to the system, the as-fitted drawings are updated to match.

What's Included

Scope of work.

  • Zone plans showing detector & device locations
  • System schematics
  • Cause-and-effect matrices
  • As-wired drawings reflecting exactly what's installed
  • Standalone documentation-only service for existing systems
  • Every drawing feeds your Digital Logbook

Viaduct Fire’s Notes

A drawing is only useful if you can find it.

Our view, from the engineer’s side of the job.

Orientation. A zone plan only does its job if the person reading it can relate it to the place they are standing in. BS 5839‑1 asks for a printed, correctly orientated zone plan on or adjacent to the indicating equipment (cl 22.2.5) but does not define “correctly orientated”. The FIA’s technical bulletin on zone plans (version 2, May 2025, written against the 2025 edition of the standard) does: the plan has to be drawn and positioned to reflect the standing position of the person looking at it, as viewed from the control and indicating equipment. With the plan on the wall and the panel shown in its true position, the building layout is rotated so that the panel sits on the top horizontal wall of the plan, which means a door shown on the left of the plan is on the left of someone standing facing the panel.

The reference point is the panel, not the main entrance. A plan drawn as if looking at the building from the main entrance is correct where the panel is by the main entrance and wrong where it is not, such as a panel in a side entrance, a plant room or a security office, because the person reading it, whether a member of staff or a firefighter, is standing at the panel. The bulletin also points out that a “You Are Here” marker, although good practice, is not a recommendation of the standard; what matters is that people can orient themselves, which showing the panel on the plan achieves, and a plan that does not align with the viewer’s position at the panel can lead to disorientation. We check orientation against the panel’s actual position on the wall when we draw a plan and again at every service visit.

Finding it. A zone plan is one document among several. BS 5839‑1 expects as-fitted drawings, operating and maintenance instructions, a cause-and-effect matrix or description and a logbook to be handed over (cl 38.1), its commentary says that without the drawings and manuals, maintenance or future modification of the system might be difficult, and anyone carrying out modifications should have the current as-fitted drawings and system configuration to hand (cl 46.1.4). Producing the documents is half of the problem and being able to find them years later is the other half. A set that was left as paper in a site office, or with the contractor who did the work, means the next person who needs it, an engineer on a fault call-out, a contractor planning an extension, an insurer or an inspector asking for certificates, has to establish who holds it before they can read it. The standard itself says the responsibility for providing documentation should be defined before an order is placed, and points to BS 8644-1 for the digital management of fire safety information, which is aimed at keeping that information relevant, accurate and accessible to the people who need it.

Our Digital Logbook. That is why we built it. Every registered site has its own secure logbook holding the zone plans, schematics and as-wired drawings we produce, kept current as the system changes, alongside service records, compliance certificates, quotes and invoices, so the documents stay with the system and not with whoever last worked on it. Weekly tests, false alarms and faults are logged against the site in one chronological record that can be filtered by type and date range, and a PDF report can be built from it for an insurer or inspector; a blank, printable logbook is available for sites that prefer paper. If you would like your site’s drawings and records brought together in one place, get in touch and we will get your site registered.

See The Digital LogbookTalk To Us About Your Site

Other Specialisms

The rest of the picture.

Fire and security systems rarely stop at one discipline — here's everything else we cover.

FA‑SYS‑01 Fire Alarms icon

Fire Alarms

Design, installation, commissioning and maintenance of fire detection and alarm systems, specified to the layout and use of your building.

Fire Alarms →
FE‑EQP‑02 Fire Extinguishers icon

Fire Extinguishers

Supply, siting and annual servicing of portable fire extinguishers, matched to the fire risks present in your building.

Fire Extinguishers →
EL‑SYS‑03 Emergency Lighting icon

Emergency Lighting

Emergency lighting that works when the power doesn't — designed, installed and tested to BS 5266‑1, so escape routes stay lit and exits stay visible.

Emergency Lighting →
CC‑SUR‑04 CCTV icon

CCTV

Camera systems specified to suit the site, with remote viewing options — from a single entrance camera to a fully networked, monitored setup.

CCTV →
IA‑DET‑05 Intruder Alarms icon

Intruder Alarms

Detection and alarm systems protecting premises against unauthorised access — from single-zone setups for smaller units to multi-zone systems across larger sites.

Intruder Alarms →
AC‑SYS‑07 Access Control icon

Access Control

Card, fob and keypad access control systems, specified to release safely on activation of your fire detection system.

Access Control →
SM‑MON‑08 Sprinkler Monitoring icon

Sprinkler Monitoring

Electrical monitoring of wet and dry sprinkler installations — flow, valve position, tank level and pump status brought back to a dedicated monitoring panel, with the signals passed on to your fire alarm system and, where required, to an ARC.

Sprinkler Monitoring →
AR‑MON‑09 ARC Monitoring icon

ARC Monitoring

Signalling from fire and intruder alarms to an accredited Alarm Receiving Centre, with police URN application support for intruder alarms.

ARC Monitoring →

Need drawing design?

Tell us about the site and what you need — we'll get back to you with a straight answer.