← Engineer Tools  /  Extinguisher Provision

Fire Extinguisher Calculator

Work out the minimum Class A rating and extinguisher count from floor area, and the right Class F extinguisher for a cooking oil hazard, per BS 5306‑8:2023.

This calculator covers Class A (floor area) and Class F (cooking oil) only. Confirm final selection against a fire risk assessment and the current edition of BS 5306‑8 (2023).

Technical Specification

Fire classes.

Extinguisher provision is matched to the classes of fire actually present on site, not a one-size-fits-all count.

ClassCoversHow it is sized
AOrdinary combustibles — wood, paper, textiles, most general office and retail risk.From floor area: 0.065 × area in m², minimum 26A per storey (calculator above). Maximum travel distance 30m.
BFlammable liquids — solvents, fuels, paints.Against the specific liquids, quantities and storage on site, not floor area. Maximum travel distance 10m.
CFlammable gases.Assessed for the specific site rather than given a fixed travel distance under the 2023 edition.
DCombustible metals.Specialist assessment of the metal and process involved; standard extinguishers are not suitable.
ElectricalFires involving live electrical equipment. Use non-conductive media only — CO₂, non-conductive powder or a clean agent.Covered by the general 30m provision, or within 10m where an extinguisher is provided specifically for an electrical hazard.
FCooking oils and fats — commercial kitchens.From the surface area of the oil, using the Class F calculator below. Maximum travel distance 10m.
LLithium-ion cells and battery packs (where no metallic lithium is present). A new class, added by BS ISO 3941:2026.No extinguisher rating or provision rule exists for this class yet. Lithium-ion guidance →

Travel distances reduce where the route to an extinguisher passes through doors, and the 2023 edition changed some of the figures for Classes C and D. Check the current edition of BS 5306‑8 for the full detail.

Class F

Cooking oil calculator.

Class F extinguishers are chosen by the surface area of the oil in the fryer or pan — not by floor area.

ExtinguisherCovers an oil surface area up to
5F0.015 m²
25F0.04 m²
40F0.06 m²
75F0.11 m²

Figures are from Fire Industry Association guidance on BS 5306‑8:2023 (clause 7.6.2, Table 2). Above 0.11 m² a single extinguisher is not enough: use several Class F extinguishers and/or a fixed suppression system, with the provision decided by a competent person. Even where a fixed system is fitted, portable Class F extinguishers are still needed for spills and for fires outside its coverage. Only Class F-rated extinguishers should be used on cooking oil fires.

Safety

The right type matters.

Never use a water extinguisher on cooking oil or live electrics, and be careful with CO₂ in small enclosed spaces and dry powder indoors. A gas fire should not be put out while the gas is still flowing — isolate the supply first, if it is safe to do so. Extinguishers should only be provided for gas risks, such as boiler houses, where your fire risk assessment calls for them and staff are trained to deal with gas fires.

Read the full safety guidance, including extinguisher pressure and condition, on our fire extinguishers page, or get in touch about staff training.

Methodology

How this is calculated.

BS 5306‑8:2023 sets the minimum Class A (ordinary combustibles) fire rating for a storey as 0.065 × the floor area in m², rounded up, with a minimum of 26A for any storey. Work out the figure for each storey separately.

At least two extinguishers are needed on a storey of 50 m² or more. Under the 2023 edition, a storey or mezzanine under 50 m² may instead have a single extinguisher, provided it is rated at least the 26A minimum. The rating can be met with any combination of extinguishers that totals the figure — for larger floors this calculator suggests 13A units as one practical way to get there, not the only one.

The maximum travel distance to the nearest extinguisher is 30m for Class A risks, and 10m for Class B and Class F risks. Extinguishers for electrical equipment are covered by the general 30m provision, or sited within 10m where they are there specifically for a hazard. Class C and Class D are assessed specifically for the site rather than given a fixed distance.

Class B (flammable liquids), Class C (gases), Class D (metals) and electrical provision is sized against the specific hazards present on site — equipment, quantities, storage — rather than floor area, so it isn't covered by these calculators. Class F is selected from the oil surface area, as above. A full provision plan should be based on a fire risk assessment covering all the hazard classes actually present in the building.

Not sure who's responsible for commissioning that assessment? See our guide: Are you the Responsible Person? →