← Engineer Tools  /  Reference Table

BS 5839‑6 Category Table

The grades and categories for fire detection in homes in BS 5839‑6:2019 — what each one means, and where each is typically used.

BS 5839‑6 covers fire detection and alarm systems in domestic premises: single-family homes, houses in multiple occupation made up of self-contained units, sheltered housing and supported housing. It doesn’t cover hostels, or the communal parts of blocks of flats and maisonettes — BS 5839‑1 applies there (see the BS 5839‑1 Category Table).

A system is described by two things: a grade, which is the engineering — how it’s powered and controlled — and a category, which is how much of the home it covers. “Grade D1, Category LD2” is a complete description; either half alone has little meaning, and the standard says both must always be stated.

The standard sets out minimum grades and categories for typical homes (Table 1), but building regulations and local authority requirements take priority where they apply, and the choice can be raised on the basis of a fire risk assessment. Ultimately, a system’s grade and category should be defined at the design stage, and revisited by risk assessment as and when needed — including when a home is extended or remodelled.

Grades

System type & power source.

GradeBS 5839‑6 definition (clause 7)Typical use (Annex C, Table 1)
AA system with control and indicating equipment to BS EN 54‑2 and power supply equipment to BS EN 54‑4, designed and installed to BS 5839‑1 (sections 1 to 4), with a few clauses replaced by their BS 5839‑6 equivalents.Where a higher standard of control and reliability is wanted, and might be appropriate where fire risk is high. Table 1 specifies it, for example, for new houses of four or more storeys and for the communal areas of HMOs.
CFire detectors and alarm sounders (which may be combined as smoke or heat alarms) connected to a common power supply — mains plus a standby supply — with central control equipment.Where central control and monitoring is wanted, such as an intruder or social alarm system with fire detectors connected, or a low-voltage system with its own control unit. The standby supply should last at least 72 hours.
D1One or more mains-powered detectors, each with a tamper-proof standby supply: a battery that isn’t designed to be removed.Recommended for rented dwellings, new or existing, because occupants of rented homes tend to be at higher risk.
D2One or more mains-powered detectors, each with an integral, user-replaceable standby battery.Recommended for new owner-occupied dwellings. Not recommended in rented dwellings, as the standby battery might be removed.
F1One or more battery-powered detectors, powered by a tamper-proof primary battery.Recommended only for existing owner-occupied dwellings.
F2One or more battery-powered detectors, powered by a user-replaceable primary battery.Recommended only for owner-occupied dwellings, where the battery is likely to be replaced promptly. Table 1 uses it for existing owner-occupied homes.

Grades B and E are “not currently defined”. The 2019 edition removed them and split Grade D and Grade F into D1/D2 and F1/F2, to separate tamper-proof batteries from user-replaceable ones; older references to a single “Grade D” or “Grade F” predate that. A requirement for one grade can be met by installing a higher grade — if Grade D is called for, Grade A or Grade C also satisfies it.

Categories

Coverage extent.

CategoryBS 5839‑6 definition (clause 8)Typical use (Table 1)
LD1Life protection. Detectors in all circulation areas that form part of the escape routes, and in all rooms and areas other than those with negligible sources of ignition, such as toilets, bathrooms and shower rooms.Single-room HMO units (bedsits), sheltered housing flats, supported housing, self-catering and short-stay guest accommodation, and new rented houses of four or more storeys.
LD2Life protection. Detectors in all circulation areas that form part of the escape routes, plus all specified rooms or areas that present a high fire risk to occupants, including any kitchen and the principal habitable room.Most homes: new owner-occupied houses and flats up to three storeys, rented houses and flats (new and existing), HMO units of two or more rooms, and HMO communal areas.
LD3Life protection. Detectors in all circulation areas that form part of the escape routes, and nowhere else.Table 1 uses it only for existing owner-occupied homes. It warns people away from a fire, but can’t be relied on to protect someone in the room where the fire starts.
PD1Property protection. Detectors in all rooms and areas where a fire might start, other than toilets, bathrooms and shower rooms.Where the owner or a property insurer wants the whole home protected. Rarely installed on its own: normally combined with an LD category.
PD2Property protection. Detectors only in defined rooms or areas where the risk of fire to property is judged to warrant them.Where specific rooms need protecting — for example a room with high-value contents. The areas protected must always be specified.

A combined system is written as X/Y — for example LD2/PD2. Definitions are summarised from clause 8 of BS 5839‑6:2019 and examples from its Annex C and Table 1, which is for typical premises and isn’t exhaustive; for the full wording, refer to the standard itself. BS 5839‑6 still cross-refers to BS 5839‑1:2017 in places; BS 5839‑1:2025 is now the current edition.

New builds, rented homes and HMOs

In England, the building regulations guidance (Approved Document B, Volume 1, paragraph 1.1) says all dwellings should have a system of at least Grade D2, Category LD3. That is the minimum for new dwellings, and it’s lower than what BS 5839‑6 itself recommends for most homes: Table 1 gives Grade D2/LD2 for new owner-occupied houses and flats, and Grade D1/LD2 for rented homes, new or existing. Larger and taller houses step up to Grade A. Wales, Scotland and Northern Ireland have their own building regulations.

HMOs are covered by both the standard and local authority requirements. Table 1 recommends, for new or altered HMOs of one or two storeys up to 200 m², Grade D1/LD1; for larger HMOs, Grade D1 detection in each unit (LD1 for single-room units, LD2 for units of two or more rooms), and Grade A, Category LD2 for the communal areas, with detectors sited to BS 5839‑1 Category L2 principles. HMOs of three or more storeys may need a mixed system, with BS 5839‑1 protection of the shared escape routes and BS 5839‑6 alarms inside each unit. Licence conditions set by the local authority can add to these, so always check the specific licence schedule.

See also the Responsible Person guide for who is responsible for fire safety in the shared parts of flats and HMOs.