BS 5839‑6 Category Table

Grades and LD categories for domestic fire detection, current to the BS 5839‑6:2019+A1:2020 revision.

Grades

System type & power source.

GradeType
AFull BS EN 54 system — control and indicating equipment, detectors and sounders on mains power with standby power per BS EN 54‑4. The highest specification, used for larger or communal systems.
CDetectors and sounders on a common power supply (mains plus standby) with a central control unit, but without a BS EN 54 control panel.
D1Mains‑powered detectors, each with a tamper‑proof, non‑replaceable standby battery (typically a sealed 10‑year lithium cell).
D2Mains‑powered detectors, each with a user‑replaceable standby battery.
F1Battery‑only detectors with a tamper‑proof primary battery.
F2Battery‑only detectors with a user‑replaceable primary battery.

Grades B and E were removed in the 2019+A1:2020 revision; Grade D and Grade F were each split into two (D1/D2 and F1/F2) to distinguish tamper‑proof from user‑replaceable batteries. Older references to a single "Grade D" or "Grade F" predate this split.

Categories

Coverage extent.

CategoryCoverage
LD1Detectors in all circulation spaces on the escape route, plus every habitable room and high‑risk area — the highest level of domestic protection.
LD2Circulation spaces on the escape route, plus specific high‑risk rooms such as the kitchen and principal living room.
LD3Circulation spaces on the escape route only — the minimum level of protection.
PDA separate property‑protection category, layered alongside an LD category where property protection is wanted in addition to life safety.

For a new‑build dwelling, Approved Document B states Grade D2, Category LD3 as the minimum considered adequate, though BS 5839‑6:2019 itself recommends the higher D1/LD2 combination as good practice. For rented and HMO properties, requirements are set by the local authority's licensing conditions rather than a single fixed figure — a common minimum specified is Grade D1/LD2, with larger or higher‑risk HMOs (three or more storeys, or five or more occupants) often requiring Grade A with LD1. Always check the specific licence schedule for the property.