Detector Spacing Calculator

Work out the applicable smoke or heat detector spacing rule for a corridor of a given width, using clause 21.2 of BS 5839‑1:2025.

Assumes a flat ceiling within the ceiling height limits in the table below. Pitched ceilings, held‑open fire doors and BS 7273‑4 can change the answer — see the notes below.

Methodology

How this is worked out.

Clause 21.2.1 of BS 5839‑1:2025 says that, under a flat ceiling, no point in a protected area should be further than 7.5m from the nearest smoke detector or 5.3m from the nearest heat detector (measured horizontally), or the figure given in BS 7273‑4 where that applies, whichever is lower.

Note 2 to the same clause relaxes this for corridors up to 2m wide, because only points close to the centre line need to be considered. There, smoke detectors can be sited at intervals of 15m and heat detectors at 10.6m, with a maximum of 7.5m (smoke) or 5.3m (heat) from the end wall. This is the same radius rule applied along a line, which is why the spacing is exactly double the radius. A corridor wider than 2m does not get the allowance and is designed to the 7.5m or 5.3m radius.

Where a corridor bends, Note 4 says it is the actual distance from each point to the nearest detector that counts, not the straight line across the corner.

Other limits

What else can change the answer.

Ceiling height. The radii above only hold up to the ceiling heights in Table 3 of the standard. Column 2 applies where the higher parts make up no more than 10% of the ceiling area.

Detector typeGenerally applicable maximum ceiling heightMaximum for up to 10% of the ceiling area
Point heat, Class A19.0m10.5m
Point heat, other classes7.5m10.5m
Point smoke10.5m12.5m
Carbon monoxide fire detectors10.5m12.5m

Optical beam and aspirating systems have their own, higher limits in the same table, set by the type and configuration of the equipment.

Pitched and apex ceilings. Under 21.2.2 the 7.5m and 5.3m distances can be increased by 1% for each degree of slope, up to a maximum of 25%, for detectors at or near the apex. Roofs with a pitch shallower than 600mm (smoke) or 150mm (heat) may be treated as flat.

Mounting depth. The sensing element should sit between 25mm and 600mm below the ceiling for smoke detectors, and 25mm to 150mm for heat detectors (21.2.4).

Held‑open fire doors. In Category L4 and L5 systems with electronically held‑open fire doors, the maximum corridor spacing recommended in BS 7273‑4 can be less than the 15m above, and the lower figure applies.

Smoke or heat? This calculator only gives the spacing for the detector type you select. In our experience smoke detection is the usual choice on escape routes because it responds earlier to a developing fire, with heat detection kept for places where smoke detectors would give false alarms, such as kitchens. That is design advice rather than a rule, so the fire risk assessment and system specification decide each case.

This tool covers the siting rule only. It does not replace a design to the standard, and the zoning, coverage and category of the system still need to be worked out for the building.