← Engineer Tools / Battery Sizing
Battery Standby Calculator
Work out the minimum standby battery capacity for a fire alarm panel from standby and alarm current readings, using the Annex E method in BS 5839‑1:2025.
Valve-regulated lead acid (VRLA) batteries only. Indicative figure — confirm final battery selection against the panel manufacturer's instructions and the current edition of BS 5839‑1.
Methodology
How this is calculated.
BS 5839‑1:2025 (clause 24.3.5) requires a fire alarm system’s standby battery to keep the system running for a set standby period, after which enough capacity must remain to give an “Evacuate” signal in all alarm zones — or, for Category P, to operate all fire alarm devices — for at least 30 minutes.
The standby period depends on the system. For a Category L or M system in most buildings it is at least 24 hours, or at least 6 hours where an automatically started standby generator serves the system. For a Category P system it is 24 hours longer than the longest period the premises are likely to be unoccupied, or 72 hours in total, whichever is less. For Category P, 24 hours is enough if the building is continuously staffed or inspected so that a power supply fault would be noticed within 6 hours, or if a power supply fault automatically sends a signal to an ARC (Alarm Receiving Centre) that notifies a keyholder immediately. Where a building may be unoccupied for longer than the battery lasts and there is an ARC link, power supply fault signals should be transmitted to the ARC automatically. See our ARC monitoring page for what’s involved, or contact us directly.
The minimum capacity of the standby (backup) battery is calculated using the formula in Annex E of the standard. The formula is for valve-regulated lead acid (VRLA) batteries — the sealed type commonly used in fire alarm panels:
Cmin (Ah) = 1.25 × [ (T1 × I1) + (D × T2 × I2) ]
T1 is the standby period in hours and I1 the standby load in amps. T2 is the alarm period (0.5 hours here) and I2 the alarm load in amps. The 1.25 factor allows for battery ageing. D is a derating factor for the higher current drawn in alarm: it can be 1 when Cmin divided by 20 is equal to or greater than the alarm load, otherwise it should be taken from the battery manufacturer’s data or be 1.75. This calculator uses 1.75 whenever the alarm load is high enough to need derating, which is the cautious figure — manufacturer data may allow a lower one.
Cmin is the capacity of the battery when new, at the 20-hour discharge rate and 20 °C. If it doesn’t match an available battery size, use the next size up; this calculator rounds up to 7, 12, 17, 24, 38, 65 or 100 Ah, but available sizes vary and must also fit the panel. Batteries other than valve-regulated lead acid are outside this method and should be sized with the battery manufacturer.
When choosing batteries, the standard asks for a type with a life of at least 4 years under the conditions of use — never automotive batteries — marked with their installation date, and with a charger able to restore the required capacity within 24 hours of full discharge (clauses 24.3.2 to 24.3.4). The 4 years is a minimum for selecting the battery, not a replacement interval: the standard sets no fixed replacement date, and instead expects batteries to be examined and load tested at each six-monthly service to check they are in good condition and unlikely to fail before the next visit (clause 43.2.7). In practice, replacement follows the battery manufacturer’s stated design life and the test results.