Sprinkler Monitoring

Electrical monitoring of wet and dry sprinkler installations — flow, valve position, tank level and pump status brought back to a dedicated monitoring panel, with the signals passed on to your fire alarm system and, where required, to an ARC. Based in Stockport, covering Greater Manchester, Cheshire and the Peak District, and sites further afield across the UK by arrangement.

The pipework and heads are installed by a specialist sprinkler contractor, to BS EN 12845, or to the LPC Rules for Automatic Sprinkler Installations, which incorporate it. We handle the electrical side: monitoring that installation and interfacing it into your fire alarm system, so activity in the sprinkler system generates an alarm signal.

That means the alarm flow switch or pressure switch, valve position (tamper) switches and low pressure switches wired back to a monitoring interface, coordinated with your fire alarm panel to BS 5839‑1, with remote signalling to an Alarm Receiving Centre set up where the building needs it.

We're based in Stockport and cover sprinkler monitoring work across Greater Manchester, Cheshire and the Peak District, with sites further afield across the UK.

STANDARD

BS EN 12845 / LPC Rules

BS EN 12845 covers the design, installation and maintenance of automatic sprinkler systems, and the LPC Rules incorporate it. Each control valve set has to have a water motor alarm and an electrical device for remote signalling (cl 16.1.1), and Annex I requires the alarms to be passed to an alarm panel in the sprinkler control room or pump room and on to a location that is permanently attended, on the premises or elsewhere. We specify and wire the interface so that signal actually reaches someone, and keep it coordinated with your fire alarm system.

Technical Specification

What each device tells you.

Sprinkler systems are often large and complex, but three devices are the ones most commonly integrated with the sprinkler alarm panel or the fire alarm system.

DeviceWhat it does
Flow switchSignals that water is flowing in the pipework, usually because a sprinkler head has operated. It is almost always configured to send a fire signal back to the sprinkler alarm panel or the fire alarm panel. A flow switch can be paired with a zone check facility, which passes water past the switch paddle to imitate a head operating, so the switch and its signalling can be tested without a head discharging.
Pressure switchMonitors the pressure in the system and operates when the pressure falls as water flows. It is a multi-purpose device: it can sound the alarm bell at the sprinkler house, monitor the system pressure during an activation, tell the jockey pump when to start, or send a fire signal to the sprinkler alarm panel or the fire alarm panel.
Isolation valvesA sprinkler system has many valves, so that the system can be drained down and worked on, and so that the water supply can be isolated in an emergency. It is essential that their open and closed positions are monitored, so that it is known whether a zone has a water supply; BS EN 12845 requires the alarm to start as soon as a normally open valve begins to close. The valves are also locked in position, traditionally with a chain or leather strap and padlock, so that they cannot be tampered with.

BS EN 12845 Annex I classes the signals as Type A (fire) or Type B (fault). Fire and fault signals are kept distinct on the way back to the fire alarm system, so a closed valve is never mistaken for an activation, or an activation for a fault.

Other Interfaces

Beyond the three devices.

Larger installations bring further signals, each with its own part to play in whether the system will work when it is needed.

InterfaceWhat it monitors
Tank water levelLow and high water levels in the supply tank, operated by a float switch of the ballcock type.
Pump monitoringFire and fault contacts are usually available on both electric and diesel pump sets: pump running, pump failure, power supply failure and low fuel level. Most modern pump sets have their own control panel, where these connections are made and configured.
Heat traceTrace heating on pipework in external areas, which stops it freezing and putting the fire protection out of action. BS EN 12845 Annex I includes the trace heating circuits among the fault signals. It is a separate system from the sprinklers themselves, and one that can easily be left off the testing schedule.

Standards

Where the two systems meet.

BS EN 12845 says what the sprinkler installation has to signal; BS 5839‑1 says how the fire alarm system should treat those signals.

STD‑01

Type A & Type B alarms — EN 12845 Annex I

Annex I defines two alarm types. Type A, the fire alarm, comes from water flow alarms and alarm valves. Type B, the fault alarm, covers technical faults that could stop the system working correctly in a fire, such as a power failure. Both have to reach a permanently attended location, and where there is a direct link to the fire and rescue service the transmission procedure is agreed with the authorities.

STD‑02

Valve supervision

Stop valves that could interrupt the supply to the sprinklers are locked in position, and under Annex H valves whose closure could stop sufficient water reaching the sprinklers, or stop an alarm or indicating device from operating, are also monitored. For normally open valves the alarm is initiated as soon as the valve starts to close, so the monitoring responds to the first movement of the valve and not only to its closed position.

STD‑03

Sprinkler signals — BS 5839‑1

BS 5839‑1:2025 recommends that filtering of signals sent to an alarm receiving centre is not applied to signals from sprinkler systems (cl 33.6.2). Where an installation initiates a fire alarm signal on flow from a single head, that head may be regarded as a heat detector for siting purposes (cl 21.2.5), provided the indication does not allow confusion with the fire detection zones and the sprinkler zone does not overlap more than one of them (cl 21.2.6).

STD‑04

Pressure surges — cl 33.6.6

Pressure surges on water mains serving sprinkler systems are listed in BS 5839‑1 among the causes of false alarms. Where a signal from a mains-fed sprinkler system is used as an input to the fire alarm system, by a pressure or flow switch for example, the standard recommends liaison with the organisation installing or maintaining the sprinkler system, and a hydraulic or electronic time delay where it is considered necessary.

What's Included

Scope of work.

  • Flow switch, pressure switch & isolation valve monitoring interfaced to your sprinkler alarm or fire alarm panel
  • Wet & dry sprinkler system alarm interfacing
  • Pump, tank level & heat trace monitoring
  • Dedicated sprinkler monitoring panels
  • Remote signalling to an Alarm Receiving Centre (ARC) where required
  • Fault-finding on existing sprinkler monitoring & interface wiring
  • Coordination with your sprinkler contractor to BS EN 12845 / LPC Rules
  • Testing & certification of the monitoring interface

Viaduct Fire’s Notes

Two systems, two panels.

Our view, from the engineer’s side of the job.

A sprinkler installation and a fire detection and alarm system are two different systems. They are installed to different standards, BS EN 12845 and BS 5839‑1, they are tested on different regimes, and they are usually maintained by different engineers, so we treat them as separate systems and, wherever the installation justifies it, give the sprinklers their own monitoring panel. BS EN 12845 is written the same way round: Annex I has the alarms passed to an alarm panel in the sprinkler control room or pump room, and on from there to a location that is permanently attended, so the starting point is a panel at the installation and not the fire alarm panel. A dedicated sprinkler monitoring panel at the installation fits that arrangement. Every input lands on it and is indicated individually, where the people who maintain the sprinklers work: flow switches, pressure switches, isolation valves, tank levels, pump fire and fault contacts, heat trace. Only summarised outputs then pass to the fire alarm system, a sprinkler fire signal and a sprinkler fault signal, which keeps the fire alarm panel from having to carry every sprinkler input individually.

The practical benefit is that each engineer can work without affecting the other’s system. A sprinkler engineer draining down a zone, closing an isolation valve, testing a flow switch or running the pumps generates signals as a matter of course, and if those inputs are wired straight onto the fire alarm panel, every one of those jobs has to be coordinated with the fire alarm: inputs disabled, the building and the alarm receiving centre warned, or the risk of a false alarm accepted. BS 5839‑1 lists testing or maintenance carried out without appropriate disablement or warning among the causes of false alarms. With a separate panel, the sprinkler engineer isolates the sprinkler interface at the sprinkler panel and the fire alarm system carries on as normal. The same holds the other way round: the fire alarm engineer can disable zones, replace a panel or reprogram the cause and effect without taking the sprinkler monitoring out of action, because the sprinkler panel is still watching the installation and still indicating an activation locally.

It also puts the BS 5839‑1 recommendations in one place. Pressure surges on mains-fed installations are a recognised cause of false alarms, and the standard recommends liaison with the sprinkler contractor and a hydraulic or electronic time delay where it is considered necessary (cl 33.6.6); that delay belongs at the sprinkler panel. Sprinkler signals sent on to an alarm receiving centre are not filtered (cl 33.6.2), and where a sprinkler head is relied on as a heat detector, its indication must not be confusable with the fire detection zones and the sprinkler zone must not overlap more than one of them (cl 21.2.6). Both systems then go on the as-fitted drawings and the cause-and-effect documentation as the separate systems they are, and both appear on the testing schedule. If you are unsure how your sprinkler monitoring is arranged, or whether the heat trace and pump signals are being tested, get in touch and we will look at it with you.

Talk To Us About Your Site

Other Specialisms

The rest of the picture.

Fire and security systems rarely stop at one discipline — here's everything else we cover.

FA‑SYS‑01 Fire Alarms icon

Fire Alarms

Design, installation, commissioning and maintenance of fire detection and alarm systems, specified to the layout and use of your building.

Fire Alarms →
FE‑EQP‑02 Fire Extinguishers icon

Fire Extinguishers

Supply, siting and annual servicing of portable fire extinguishers, matched to the fire risks present in your building.

Fire Extinguishers →
EL‑SYS‑03 Emergency Lighting icon

Emergency Lighting

Emergency lighting that works when the power doesn't — designed, installed and tested to BS 5266‑1, so escape routes stay lit and exits stay visible.

Emergency Lighting →
CC‑SUR‑04 CCTV icon

CCTV

Camera systems specified to suit the site, with remote viewing options — from a single entrance camera to a fully networked, monitored setup.

CCTV →
IA‑DET‑05 Intruder Alarms icon

Intruder Alarms

Detection and alarm systems protecting premises against unauthorised access — from single-zone setups for smaller units to multi-zone systems across larger sites.

Intruder Alarms →
DS‑DOC‑06 Drawing Design icon

Drawing Design

Zone plans, system schematics and as-wired drawings for new and existing systems — available as a standalone service for systems that need documentation brought up to date.

Drawing Design →
AC‑SYS‑07 Access Control icon

Access Control

Card, fob and keypad access control systems, specified to release safely on activation of your fire detection system.

Access Control →
AR‑MON‑09 ARC Monitoring icon

ARC Monitoring

Signalling from fire and intruder alarms to an accredited Alarm Receiving Centre, with police URN application support for intruder alarms.

ARC Monitoring →

Need sprinkler monitoring?

Tell us about the site and what you need — we'll get back to you with a straight answer.